Cable Glands

Industrial and Hazardous Area Cable Glands

Contact us now at sales@engineeringpowersolutions.co.uk to place an order, pricing or technical data sheets. We have 1000’s of different types of industrial and hazardous area cable glands available, our popular cable glands manufacturers include HAWKE and CMP products.

All types of HAWKE & CMP Cable glands in stock! Contact us now for a quotation.

 

HAWKE 501/421 Cable Gland

Flameproof Exd / Increased Safety Exe / Dust Extb / Dual Certified ATEX – IECEx

121-421

Datasheet (click here)

Application

The 501/421 cable gland provides a seal on the outer cable sheath and is intended for use on non-armoured elastomer and plastic insulated cables. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

Features
When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure. The braid must be suitably terminated inside the enclosure.

Materials & Finishes
The 501/421 cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Technical Data
Exd IIC Gb, Exe IIC Gb, Extb IIIC Db
Certificate No’s
Baseefa06ATEX0056X and IECEx BAS 06.0013X.
Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31.
Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge Protection to:
DTS01
Operating Temperature Range:
-60°C to +100°C
Assembly Instruction Sheet:
AI 307.

 

HAWKE 501/423 Cable Gland

Flameproof Exd / Increased Safety Exe / Dust Extb / Dual Certified ATEX – IECEx

123-423

Datasheet (click here)

Application

The 501/423 cable gland provides two independent seals on non-armoured elastomer and plastic insulated cables. The first is a flameproof seal on the inner or outer cable sheath, with an additional IP seal on the outer sheath. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

Features
Provides superior cable retention to standard unarmoured cable glands, with seal at two independent points. When used in increased safety applications, this cable gland may be used with braided cable where the braid and the outer sheath pass into the enclosure. The braid must be suitably terminated inside the enclosure.

Materials & Finishes
The 501/423 cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Technical Data
Exd IIC Gb, Exe IIC Gb, Extb IIIC Db
Certificate No’s
Baseefa06ATEX0056X and IECEx BAS 06.0013X.
Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31.
Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge Protection to:
DTS01
Operating Temperature Range:
-60°C to +100°C
Assembly Instruction Sheet:
AI 306.

 

HAWKE 501/453/RAC Cable Gland

Flameproof Exd / Increased Safety Exe / Dust Extb / Dual Certified ATEX – IECEx

153-453-rac

Datasheet (click here)

Application

Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.

Features
Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a seal on the cables inner sheath.
Deluge protection option available, contact Hawke Technical Sales for details.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

Materials & Finishes
The 501/453/RAC cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Technical Data
Exd IIC Gb, Exe IIC Gb, Extb IIIC Db
Certificate No’s
Baseefa06ATEX0056X and IECEx BAS 06.0013X.
Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31.
Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge Protection to:
DTS01 (Deluge seal optional).
Operating Temperature Range:
-60°C to +100°C
Assembly Instruction Sheet:
AI 302.

 

HAWKE 501/453/RAC/L Cable Gland

Flameproof Exd / Increased Safety Exe / Dust Extb / Dual Certified ATEX – IECEx

153-453-racl

Datasheet (click here)

Application

Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.

Features
Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Deluge protection option available, contact Hawke Technical Sales for details.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

Materials & Finishes
The 501/453/RAC/L cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Technical Data
Exd IIC Gb, Exe IIC Gb, Extb IIIC Db
Certificate No’s
Baseefa06ATEX0056X and IECEx BAS 06.0013X.
Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31.
Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge Protection to:
DTS01 (Deluge seal optional).
Operating Temperature Range:
-60°C to +100°C
Assembly Instruction Sheet:
AI 302 & AI336.

Case Studies

Testimonials

Membership: